ESIE09-08
Field Setting
Test Operation
81
3. Field Setting
3.1 Field Setting from remote control
Individual function of indoor unit can be changed from the remote control. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired remote control
BRC21A51
To change one or more field settings, proceed as follows.
1. Press the
z
button for a minimum of 5 seconds to enter FIELD SET MODE.
The
$
icon (c) will be displayed. The current selected field setting code is indicated
;
(b), with the set value displayed to the right
-
(a).
2. Press the
ébi
button to select the appropriate field setting first code (
8-
).
3. Press the
ébj
button to select the appropriate field setting second code (
-88
).
4. Press the
pfi
button and
pfj
button to change the set value of the select field
setting.
5. Save the new value by pressing the
pr
button.
6. Repeat step 2 through 4 to change other field settings as required.
7. When finished, press the
z
button to exit FIELD SET MODE.
b
1
c
a
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...