Troubleshooting by Indication on the Remote Controller
ESIE09-08
134
Troubleshooting
3.4
“AJ”
Indoor Unit: Malfunction of Capacity Determination
Device
Remote Control
Display
AJ
Subcode 0
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adapter and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
Operation and:
1. When the capacity code is not contained in the PC board’s memory, and the capacity setting
adapter is not connected.
2. When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
You have forgotten to install the capacity setting adapter.
Defect of indoor unit PC board (A4P).
Troubleshooting
(V2783)
Caution
Install a capacity setting adapter.
Replace the indoor unit PC board.
(A4P)
NO
NO
YES
YES
Replace the indoor unit PC
board. (A4P)
The indoor
unit PC board was
replaced with a replacement
PC board.
The
indoor unit is a
model that requires
installation of a capacity
setting adapter when
replacing the PC
board.
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...