ESIE09-08
Troubleshooting by Indication on the Remote Controller
Troubleshooting
139
3.8
“C9”
Indoor Unit: Return Water Thermistor (R4T)
Remote Control
Display
C9
Subcode 0
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by return water temperature
thermistor.
Malfunction
Decision
Conditions
When the return water temperature thermistor becomes disconnected or shorted while the unit
is running.
Supposed
Causes
Defect of indoor unit thermistor (R4T) for water return
Defect of indoor unit PC board (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P229.
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Replace the indoor unit PC board (A1P).
Connect the thermistor and turn
on again.
Faulty thermistor
value > 95 C
NO
NO
Replace the thermistor (R4T).
YES
YES
Connector is
connected to X12A of
the indoor unit PC
board.
Resistance
is normal when
measured after
disconnecting the thermistor
(X12A) (R4T) from the
indoor unit PC board.
(7.2k ~112k )
(V2786)
Bad wire connection
value < -43.6 C
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...