Field Setting
ESIE09-08
98
Test Operation
[A] Option setup
[A-02]
Temperature difference for leaving and returning water
The unit is designed to support radiator operation. The advised leaving water temperature
(set by the remote controller) for radiators is 65°C. In such a case the unit will be controlled
to realize a temperature difference (
Δ
T) of 10°C, which means that the returning water to the
unit is around 55°C.
Depending on the installed application (radiators, fan coil units, ...) or situation, it can be
required to change the
Δ
T. This can be done by changing field setting [A-02].
[A-03]
Multi set point 1 temperature.
[A-04]
Multi set point 2 temperature.
Notes :
1. When temperature reducing devices are installed, the system can be configured to use multi
set points, also the demand PCB (option) is needed.
2. The selected values for multiple set point should be lower than the value from remote
controller (reference temperature) or domestic hot water temperature (pattern A).
3. Daikin does not offer any temperature reducing device (TRD). This system (multi set point
control) only provides the possibility to use multi set point. It’s than also the installers
responsibility to make sure that the whole system is operating well.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
A
Option setup
02
Set point: required temperature difference for
leaving and returning water
10
5~15
1
°C
03
Set point: multiple set point 1 required
temperature value
35
25~80
1
°C
04
Set point: multiple set point 2 required
temperature value
65
25~80
1
°C
Summary of Contents for ERSQ 011AAV1
Page 2: ......
Page 12: ...Introduction ESIE09 08 x...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08 4 General Information...
Page 22: ...Specifications ESIE09 08 10 Specifications...
Page 38: ...Functional Parts Layout ESIE09 08 26 Refrigerant Circuit...
Page 248: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08 236 Appendix...