11
|
Configuration
Installer reference guide
195
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
#
Code
Description
[9.8.2]
[D-00]
Allow heater
: Which heaters are allowed to
operate during preferential kWh rate power
supply?
▪
0
No
: None
▪
1
Only BSH
: Booster heater only
▪
2
Only BUH
: Backup heater only
▪
3
All
: All heaters
See table below.
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or indoor unit
is connected to a normal kWh rate power supply
(via X2M/5‑6) and the backup heater is NOT
connected to the preferential kWh rate power
supply.
[9.8.3]
[D-05]
Allow pump
:
▪
0
No
: Pump is forced off
▪
1
Yes
: No limitation
Allowed heaters during preferential kWh rate power supply
Do NOT use 1 or 3. Setting [D-00] to 1 or 3 when [D-01] is set to 1 or 2 will reset
[D-00] back to 0, as the system does not have a booster heater. Only set [D-00] to
the values in the table below:
[D‑00]
Backup heater
Compressor
0
Forced OFF
Forced OFF
2
Allowed
Power consumption control
Power consumption control
See
28] for detailed information about this
functionality.
#
Code
Description
[9.9.1]
[4-08]
Power consumption control
:
▪
0
No
: Disabled.
▪
1
Continuous
: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
▪
2
Inputs
: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
▪
3
Current sensor
: Enabled: You can set a
current limitation value (in A) to which the
household current will be limited.