11
|
Configuration
Installer reference guide
168
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
#
Code
Description
[3.A]
[C‑06]
External room thermostat type for the additional
zone:
▪
1:
1 contact
. Connected to only 1 digital
input (X2M/35a)
▪
2:
2 contacts
. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
Leaving water temperature: Delta T
#
Code
Description
[3.B.1]
[1-0C]
Delta T heating
: A minimum temperature
difference is required for the good operation of
heat emitters in heating mode.
▪
3°C~10°C
[3.B.2]
[1-0E]
Delta T cooling
: A minimum temperature
difference is required for the good operation of
heat emitters in cooling mode.
▪
3°C~10°C
WD curve type
There are 2 methods to define the weather-dependent curves:
▪
2-points
148])
▪
Slope-Offset
In [2.E]
WD curve type
, you can choose which method you want to use.
In [3.C]
WD curve type
, the chosen method is shown read-only (same value as in
[2.E]).
#
Code
Description
[2.E] / [3.C]
N/A
▪
2-points
▪
Slope-Offset
11.5.5 Space heating/cooling
About space operation modes
Your unit can be a heating or a heating/cooling model:
▪
If your unit is a heating model, it can heat up a space.
▪
If your unit is a heating/cooling model, it can both heat up and cool down a
space. You have to tell the system which operation mode to use.
To determine if a heating/cooling heat pump model is installed
1
Go to [4]:
Space heating/cooling
.
2
Check if [4.1]
Operation mode
is listed and editable. If so, a
heating/cooling heat pump model is installed.
To tell the system which space operation to use, you can:
You can…
Location
Check which space operation mode is currently used. Home screen