6
|
Application guidelines
Installer reference guide
41
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
2 (
Room thermostat
): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Note:
▪
Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪
Other rooms = external room
thermostat functionality
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
1 (
Dual zone
): Main + additional
In case of heat pump convectors:
External room thermostat for the
additional
zone:
▪
#: [3.A]
▪
Code: [C-06]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Shut-off valve output
Set to follow the thermo demand of the
main zone.
Shut-off valve
If the main zone must be shut off during
cooling mode to prevent condensation
on the floor, set it accordingly.
At the mixing valve station
Set the desired main leaving water
temperature for heating and/or cooling.
Benefits
▪
Comfort.
-
The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature
(modulation).
-
The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heat pump convectors.
▪
Efficiency.
-
Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.