11
|
Configuration
Installer reference guide
181
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
In case of
Schedule only
or
Schedule + reheat
domestic hot water
preparation, the storage comfort temperature is weather-dependent (according to
the weather-dependent curve), the storage economic and reheat temperature are
NOT weather-dependent.
In case of
Reheat only
domestic hot water preparation, the desired tank
temperature is weather-dependent (according to the weather-dependent curve).
During weather-dependent operation, the end-user cannot adjust the desired tank
temperature on the user interface. Also see
148] and
#
Code
Description
[5.C]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
WD curve
:
Note:
There are 2 methods to set the weather
dependent curve. See
149] for more information about the
different curve types. Both curve types require 4
field settings to be configured according to the
figure below.
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E]
[0-0D]
▪
T
DHW
: The desired tank temperature.
▪
T
a
:
The
(averaged)
outdoor
ambient
temperature
▪
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
▪
[0-0D]: high outdoor ambient temperature:
10°C~25°C
▪
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: Min(45,[6-0E])°C
~[6-0E]°C
▪
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C