6/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.6.6
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.6.7
[8-04]
R/W
0~95 min, step: 5 min
95 min
Installer settings
9.7
[4-04]
R/O
0: Intermittent
1: continuous
2: Disabled
└─
Benefit kWh power supply
9.8.1
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
9.8.2
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.8.3
[D-05]
R/W
0: Forced off
1: As normal
└─
Power consumption control
9.9.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
3: Current sensors
9.9.2
[4-09]
R/W
0: Current
1: Power
9.9.3
[5-05]
R/W
0~50 A, step: 1 A
16 A
9.9.4
[5-05]
R/W
0~50 A, step: 1 A
16 A
9.9.5
[5-06]
R/W
0~50 A, step: 1 A
16 A
9.9.6
[5-07]
R/W
0~50 A, step: 1 A
16 A
9.9.7
[5-08]
R/W
0~50 A, step: 1 A
16 A
9.9.8
[5-09]
R/W
0~20 kW, step: 0,5 kW
5 kW
9.9.9
[5-09]
R/W
0~20 kW, step: 0,5 kW
5 kW
9.9.A
[5-0A]
R/W
0~20 kW, step: 0,5 kW
5 kW
9.9.B
[5-0B]
R/W
0~20 kW, step: 0,5 kW
5 kW
9.9.C
[5-0C]
R/W
0~20 kW, step: 0,5 kW
5 kW
9.9.D
[4-01]
R/W
0: None
1: BSH
2: BUH
9.9.E
[4-0E]
R/W
-6~6A, step: 0,5 A
0 A
9.9.F
[7-07]
R/W
0: Disabled
1: Enabled
└─
Energy metering
9.A.1
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.A.2
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
└─
Sensors
9.B.1
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.B.2
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.B.3
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Bivalent
9.C.1
[C-02]
R/W
0: No
1: Bivalent
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Normally open
1: Normally closed
9.E
[3-00]
R/W
0: No
1: Yes
9.F
[E-08]
R/O
0: disabled
1: Enabled
9.G
R/W
0: No
1: Yes
└─
Overview field settings
Maximum running timer
Additional timer
Water pipe freeze prevention
Benefit kWh power supply
Allow heater
Allow pump
Power consumption control
Type
Limit
Limit 1
Limit 2
Limit 3
Limit 4
Limit
Limit 1
Limit 2
Limit 3
Limit 4
Priority heater
Electricity meter 1
Electricity meter 2
External sensor
BBR16 limit activated?
Ext. amb. sensor offset
Averaging time
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
Auto restart
Power saving function
Disable protections
Current sensor offset
4P675763-1 - 2021.10
(*1) *X*_(*2) *H*