12
|
Commissioning
Installer reference guide
209
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Typical workflow
Commissioning typically consists of the following stages:
1
Checking the “Checklist before commissioning”.
2
Performing an air purge on the water circuit.
3
Performing an air purge on the central water loop circuit.
4
Performing a test run for the system.
5
If necessary, performing a test run for one or more actuators.
6
If necessary, performing an underfloor heating screed dryout.
12.2 Precautions when commissioning
INFORMATION
During the first running period of the unit, the required power may be higher than
stated on the nameplate of the unit. This phenomenon is caused by the compressor,
that needs a continuous run time of 50 hours before reaching smooth operation and
stable power consumption.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT,
burning of the compressor might be the result.
12.3 Checklist before commissioning
1
After the installation of the unit, check the items listed below.
2
Close the unit.
3
Power up the unit.
INFORMATION
When (re)starting the unit, it takes 7 minutes to initialise the software. The
compressor only turns on after the software is initialised.
You read the complete installation instructions, as described in the
installer reference
guide
.
The
indoor unit
is properly mounted.
The following
field wiring
has been carried out according to this document and the
applicable legislation:
▪
Between the local supply panel and the indoor unit
▪
Between the indoor unit and the valves (if applicable)
▪
Between the indoor unit and the room thermostat (if applicable)
The system is properly
earthed
and the earth terminals are tightened.
The
fuses
or locally installed protection devices are installed according to this document,
and have NOT been bypassed.
The
power supply voltage
matches the voltage on the identification label of the unit.
There are NO
loose connections
or damaged electrical components in the switch box.
There are NO
damaged components
or
squeezed pipes
on the inside of the indoor unit.