9
|
Electrical installation
Installer reference guide
85
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Item
Description
Thermostat for passive
cooling
See
"9.2.12 To connect the thermostat for passive
LAN adapter connections
See
105].
Room thermostat (wired or
wireless)
See:
▪
Installation manual of the room thermostat
(wired or wireless)
▪
Addendum book for optional equipment
Wires for wired room thermostat: (3 for
cooling/heating operation; 2 for heating only
operation)×0.75 mm²
Wires for wireless room thermostat: (5 for
cooling/heating operation; 4 for heating only
operation)×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪
[2.9]
Control
▪
[2.A]
Ext thermostat type
For the additional zone:
▪
[3.A]
Ext thermostat type
▪
[3.9] (read-only)
Control
Heat pump convector
See:
▪
Installation manual of the heat pump
convectors
▪
Addendum book for optional equipment
Wires: 4×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪
[2.9]
Control
▪
[2.A]
Ext thermostat type
For the additional zone:
▪
[3.A]
Ext thermostat type
▪
[3.9] (read-only)
Control
Remote indoor sensor
See:
▪
Installation manual of the remote indoor
sensor
▪
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset