11
|
Configuration
Installer reference guide
192
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
#
Code
Description
[9.5.2]
[7-06]
Activation of the
Compressor forced off
mode:
▪
0:
disabled
▪
1:
enabled
NOTICE
Activating
Compressor forced off
mode will NOT stop or prevent the central
water loop pump from operating in the following conditions:
▪
The
Water loop valve
test run has been started
▪
Passive cooling is active
Balancing
Priorities
For systems with an integrated domestic hot water tank.
#
Code
Description
[9.6.1]
[5‑02]
Space heating priority
: Defines
whether backup heater will assist the heat
pump during domestic hot water operation.
For optimal operation and lowest power
consumption, it is strongly recommended to
keep the default setting (
0
).
If the backup heater operation is limited
([4‑00]=0) and the outdoor temperature is
lower than setting [5‑03], the domestic hot
water will not be heated with the backup
heater.
[9.6.2]
[5‑03]
Priority temperature
: Used for
calculation of anti-recycling timer. If [5‑02]=1, it
defines the outdoor temperature below which
the backup heater will assist during domestic
hot water heating.
[5‑01] Equilibrium temperature and [5‑03]
Space heating priority temperature are related
to backup heater. So, you must set [5‑03] equal
or a few degrees higher than [5‑01].
Timers
For simultaneous space and domestic hot water operation request.
[8-02]:
Anti-recycle timer
t
1
0
1
0
[8-01]
[8-02]