10
|
LAN adapter
Installer reference guide
111
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Connectors
X4A
4
N
L
3
2
1
2
1
X1A
X2A
X3A
a1
b
c
a2
d
a1
To solar inverter/energy management system
a2
230 V AC detection voltage
b
To electricity meter
c
Factory-mounted cable to indoor unit (P1/P2)
d
To router (via the factory-mounted Ethernet cable outside of the unit)
Connections
Field-supplied cables:
Connection
Cable section
Wires
Maximum cable
length
Router (via the
factory-mounted
Ethernet cable
outside of the unit,
which is coming
from X4A)
—
—
50/100 m
(a)
Electricity meter
(X2A)
0.75~1.25 mm
2
2
(b)
100 m
Solar inverter/
energy
management
230 V AC
detection voltage
(X1A)
0.75~1.5 mm
2
Depends on
application
(c)
100 m
(a)
Ethernet cable: respect the maximum allowed distance between LAN adapter and router,
which is 50 m in case of Cat5e cables, and 100 m in case of Cat6 cables.
(b)
These wires MUST be sheathed. Recommended strip length: 6 mm.
(c)
All wiring to X1A MUST be H05VV. Required strip length: 7 mm. For more information, see
"10.2.4 Solar inverter/energy management system"
10.2.2 Router
Make sure the LAN adapter can be connected via a LAN connection.
The minimum category for the Ethernet cable is Cat5e.
To connect the router
Use one of the following ways (A, B or C) to connect the router: