Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. This setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location.
#
Code
Description
[9.B.2]
[2-0B]
Ext. amb. sensor offset
: Offset on the
ambient temperature measured on the external
outdoor temperature sensor.
▪
–5°C~5°C, step 0.5°C
Averaging time
The average timer corrects the influence of ambient temperature variations. The
weather-dependent setpoint calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
Description
[9.B.3]
[1-0A]
Averaging time
:
▪
0: No averaging
▪
1: 12 hours
▪
2: 24 hours
▪
3: 48 hours
▪
4: 72 hours
Brine low pressure switch
When a brine low pressure switch is installed, the unit must be configured to work
with the switch. When the switch is removed or disconnected, this setting must be
set to OFF.
#
Code
Description
N/A
[C-0B]
Activation of the brine low pressure switch
▪
0: OFF
▪
1: On
Bivalent
Bivalent
Only applicable in case of auxiliary boiler.
NOTICE
Bivalent operation is only possible if:
▪
Space heating is turned ON, and
▪
DHW tank operation is turned OFF.