11
|
Configuration
Installer reference guide
196
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Continuous power consumption control and power consumption control with
digital inputs
The type of limit needs to be set in combination with the continuous power
consumption control and the power consumption control with digital inputs.
#
Code
Description
[9.9.2]
[4-09]
Type
:
▪
0
Amp
: The limitation values are set in A.
▪
1
kW
: The limitation values are set in kW.
Limit when [9.9.1]=
Continuous
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.3]
[5-05]
Limit
: Only applicable in case of full time
current limitation mode.
0 A~50 A
Limits when [9.9.1]=
Inputs
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.4]
[5-05]
Limit 1
: 0 A~50 A
[9.9.5]
[5-06]
Limit 2
: 0 A~50 A
[9.9.6]
[5-07]
Limit 3
: 0 A~50 A
[9.9.7]
[5-08]
Limit 4
: 0 A~50 A
Limit when [9.9.1]=
Continuous
and [9.9.2]=
kW
:
#
Code
Description
[9.9.8]
[5-09]
Limit
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Limits when [9.9.1]=
Inputs
and [9.9.2]=
kW
:
#
Code
Description
[9.9.9]
[5-09]
Limit 1
: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 2
: 0 kW~20 kW
[9.9.B]
[5-0B]
Limit 3
: 0 kW~20 kW
[9.9.C]
[5-0C]
Limit 4
: 0 kW~20 kW
Power consumption control via current sensors
Limit when [9.9.1]=
Current sensor
:
#
Code
Description
[9.9.3]
[5-05]
Limit: 0 A~50 A
In case the current sensors are calibrated, you can specify an offset for the output
of the current sensors. This value will be added to the current output value of the
current sensor.