Electrical installation
Installer reference guide
103
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
NOTICE
Before disconnecting.
If you want to remove or disconnect the brine low pressure
switch, first set [C‑0B]=0 (brine low pressure switch not installed). If not, this causes
an error.
1
Open the following (see
"7.2.2 To open the indoor unit"
1
Top panel
1
3
2
2
User interface panel
3
Installer switch box cover
2
Connect the brine low pressure switch cable as shown in the illustration
below.
2×
1×
A16P/X13A/1+4
1×
S1PL
P<
b
a
c
a
Cut loop wires coming from A16P/X13A/1+4 (factory mounted)
b
Splicing connectors (field supply)
c
Wires from the brine low pressure switch cable (field supply)
3
Fix the cable with cable ties to the cable tie mountings.