f.
Verify the updated settings have been written.
smw$
cat manual_valve_pos
49
- The
cat
command shows the percentage used in
3. Open the rear door of the cabinet.
4. Cut the tie straps that secure the water valve actuator cable to the adjacent control cables, if necessary.
5. Verify the water valve is in the fully closed position.
6. Place a long piece of tape over the actuator indicator dial to hold it in place.
7. Remove the Phillips screw that attaches the actuator to the valve and remove the actuator.
8. Disconnect the water valve actuator control cable from the coil control board.
2.19.2 Install a Spring Returned Water Valve Actuator
Prerequisites
Tools Required:
Diagonal cutter
Tie straps
Phillips screwdriver
Hex-head tool
Time Required:
8-10 minutes
About this task
CAUTION:
●
Equipment damage
●
It's recommended to perform this procedure on a powered down cabinet. If performed on a powered
up cabinet, the actuator must be replaced within 15-20 minutes to prevent possible system EPO and/
or condensation.
CAUTION:
●
Equipment damage
●
This procedure is affected by the current power consumption and utilization of the system. Be
cautious of workload increases or decreases. Significant workflow changes that occur after the
system is in manual mode could lead to cabinet EPO and/or condensation.
System Cabinet Procedures
82