Figure 149. KPDC Standoffs
4. Record the location of the DIMMs and processors on the defective KPDC to reinstall them in the same
locations on the replacement KPDC.
5. Remove the processors and DIMMs from the defective KPDC.
6. Install the processors and DIMMs on the replacement KPDC.
7. Place the processor air ducts and position the power cable assembly on the blade.
8. Install the power cable assembly.
a. Position the power cable assembly on the blade.
b. Insert the two tabs on the center of the cable into the standoffs on the blade.
c. Reconnect the cable connectors.
9. Replace the air diffuser bracket and reinstall the T10 Torx screws. Torque screws to 5.5 in-lbs.
10. Replace the shroud and reinstall the T15 Torx attachment screws. Torque to 9 in-lbs.
11. Reinstall the blade into the cabinet.
Compute and IO Blade Procedures