7. Close the front door of the cabinet.
8. Power up all of the cabinets in the row.
a. For blower cabinets, place the MAIN DISCONNECT switch on the rear panel of the blower cabinet PDU
in the ON (up) position.
b. For cabinets, place main circuit breakers CB1 and CB2 in the ON (up) position.
Figure 51. Circuit Breakers for Cabinet (left) and Blower (right)
a. Close the rear door of the cabinet.
b. Enter the following command in a terminal window on the SMW:
smw$
xtcli power up Hostname
Hostname
is the cabinet, system, or partition ID; examples include
c0-0
(for a cabinet),
S0
(for a
system), or
p0
(for a partition).
2.12 Cabinet Controller DIMM Replacement
2.12.1 Remove a Cabinet Controller DIMM
Prerequisites
Tools Required:
T15 Torx bit
Adjustable torque driver, 5-40 in-lbs
Small slotted screwdriver
Dusting gas
Time Required:
5 minutes
Procedure
1. Power down all of the cabinets in the row.
a. Enter the following command in a terminal window on the SMW:
smw$
xtcli power down Hostname
System Cabinet Procedures
58