FRP 25: Thermostat Replacement
AC Repair and Adjustment Procedures
144
Cray Research/Silicon Graphics Proprietary
HMM-168-A
b. Ensure that the thermostat trips CB1 at a temperature above the
high-fault temperature for the exhaust air thermistors.
c. Allow the thermostat to cool to less than 100˚ F (38˚ C), then reset
CB1.
7.
Replace the upper plenum panel and the module panel.
8.
Replace the blower shield and connect the cable to the clock switch
board.
9.
Return the cabinet to normal operation, and close both cabinet doors.
WARNING
The thermostats receive line voltage.
Do not contact them. Failure to avoid
the thermostats and thermostat wires
could result in severe shocks and
burns.