AC Repair and Adjustment Procedures
FRP 16: WACS Scanner Board Replacement
HMM-168-A
Cray Research/Silicon Graphics Proprietary
115
scanner by the transformer end.
11. Remove the scanner from the cabinet and place it in an ESD-protective
bag.
Scanner Installation
1.
Remove the replacement scanner from the ESD-protective bag.
2.
Position the scanner in the WACS box, and align the screw holes.
3.
Replace the screws and washers; tighten them.
4.
Replace the power strip connector using the following procedure:
NOTE:
This procedure is more difficult than it looks. Work carefully
and ensure that you do not bend the pins and that the connector
is fully inserted.
a. Position the power strip for connection to the WACS scanner. To
improve insertion, hold the power strip at a slight angle (~5˚), with the
socket end closer to the floor.
b. Gently press the power strip horizontally into the scanner portion of
the power connector. Ensure that the sockets align with the pins and
that the tabs on the top of the power strip stay on the outside (top) of
the scanner portion of the connector. Refer to
.
c. Carefully place the fingers of both hands on the back of the scanner
PCB to provide support while you use your thumbs to push the power
strip firmly into position on the scanner. Be careful not to push too
hard, but also be sure that you complete the connection.
5.
Connect the WACS connectors (Amp-modu connectors): push the
connectors horizontally into the scanner connectors until the side latches
snap into place.
The connectors are tabbed so that you can insert them one way only.
6.
Close the WACS panel.
Rotate the two latch screws counterclockwise to secure the panel.
7.
Power up the cabinet and check WACS function.
8. Close the front cabinet door.