FRP 16: WACS Scanner Board Replacement
AC Repair and Adjustment Procedures
114
Cray Research/Silicon Graphics Proprietary
HMM-168-A
You may also open, lock, and tag the customer’s wall breaker(s).
3.
Open the WACS panel. (Rotate the two latch screws clockwise to release
the panel. You may need a flatblade screwdriver.)
4.
Note the positions of the connectors on the defective WACS scanner.
5.
Remove the replacement scanner from the ESD-protective bag.
6.
Set the DIP switches on the replacement scanner to match those on the
defective scanner.
7.
Replace the replacement scanner in the ESD-protective bag.
8.
Disconnect the WACS connectors (Amp-modu connectors) from the
defective WACS scanner:
a. Pull the side latches away from the connectors as shown in
b. Pull the connectors with firm, even pressure to disconnect them from
the WACS scanner.
c. Move the connectors to the side.
Figure 54. WACS Scanner Connector
9.
Remove the power strip connector from the defective WACS scanner by
pulling horizontally, straight out from the scanner. It may help to pull one
end out first and then the other.
10. Remove the 6 Phillips screws (and washers) that hold the scanner board.
Hold the scanner in place while you remove the last 2 screws. Hold the
Step 8