Chapter 4 — Sequence of Operation
Part No. 750-184
4-5
closed at this time, or if they subsequently open, the program relay will go
into a safety shutdown.
At the completion of the high fire purge period, the program relay signals the
modulating damper motor (MDM) to drive the air damper to its low fire
position.
To assure that the system is in low fire position prior to ignition, the low fire
switch (LFS) must be closed to complete the “low fire proving circuit.” The
sequence will stop and hold until the modulating damper motor (MDM) has
returned to the low fire position and the contacts of the low fire switch (LFS)
are closed. Once the low fire switch is closed, the sequence is allowed to
continue.
Notice
Note: The ignition trial cannot be started if flame or a flame
simulating condition is sensed during the pre-purge period.
A safety shutdown will occur if flame is sensed at this time.
Ignition Cycle -
The ignition transformer (IT) and gas pilot valve (GPV) are
energized from the appropriate pilot ignition terminal.
Notice
Note: An oil-fired burner may be equipped with an oil pilot
rather than a gas pilot. The ignition sequence of both is
identical.
The pilot flame must be established and proven by the flame detector (FD)
within a 10 second period in order for the ignition cycle to continue. If for
any reason this does not happen, the system will shut down and safety
lockout will occur.
Notice
Note: Depending upon the requirements of the regulatory
body, insurer or fuel being burned, either the 10 or 15
second pilot ignition terminal may be used. Both provide the
same function but differ in time interval allowed for proving
main flame ignition. Refer to the boiler wiring diagram.
With a proven pilot, the main fuel valve(s) (OV or MGV) is energized and the
main fuel valve light (FVL) in the panel is lighted. The main flame is ignited
and the trial period for proving the main flame begins. It lasts 10 seconds
for light oil and natural gas, and 15 seconds for heavy oil. At the end of the
proving period, if the flame detector still detects main flame, the ignition
transformer and pilot valve are deenergized and pilot flame is extinguished.
Notice
Note: If the main flame does not light, or stay lit, the fuel
valve will close. The safety switch will trip to lock out the
control. Refer to flame loss sequence (section D) for
description of action.
!
Warning
The cause for loss of flame or any other unusual condition should be
investigated and corrected before attempting to restart. Failure to
Summary of Contents for CB Ohio Special 100 HP
Page 2: ...ii ...
Page 8: ...viii ...
Page 42: ...Chapter 2 Burner Operation and Control 2 22 Part No 750 184 ...
Page 116: ...Chapter 6 Adjustment Procedures 6 28 Part No 750 184 ...
Page 126: ...Chapter 8 Inspection and Maintenance 8 6 Part No 750 184 ...
Page 153: ...Chapter 9 Parts Part No 750 184 9 3 Insulated Front Head Model CB LE ...
Page 154: ...Chapter 9 Parts 9 4 Part No 750 184 Insulated Front Head Interior Model CB LE ...
Page 155: ...Chapter 9 Parts Part No 750 184 9 5 Insulated Inner Door Model CB OS ...
Page 156: ...Chapter 9 Parts 9 6 Part No 750 184 Insulated Rear Head CB LE ...
Page 157: ...Chapter 9 Parts Part No 750 184 9 7 Insulated Rear Head CB LE ...
Page 158: ...Chapter 9 Parts 9 8 Part No 750 184 Insulated Rear Head CB OS ...
Page 159: ...Chapter 9 Parts Part No 750 184 9 9 Dry Oven Model CB LE ...
Page 161: ...Chapter 9 Parts Part No 750 184 9 11 Motor Impeller Model CB LE ...
Page 162: ...Chapter 9 Parts 9 12 Part No 750 184 Front Head Linkage ...
Page 170: ...Chapter 9 Parts 9 20 Part No 750 184 Control Cabinet Hawk ICS ...
Page 171: ...Chapter 9 Parts Part No 750 184 9 21 Control Panel Standard ...
Page 172: ...Chapter 9 Parts 9 22 Part No 750 184 Entrance Box ...
Page 173: ...Chapter 9 Parts Part No 750 184 9 23 Front Head Electrical CB LE ...
Page 174: ...Chapter 9 Parts 9 24 Part No 750 184 Front Head Electrical CB LE ...
Page 175: ...Chapter 9 Parts Part No 750 184 9 25 Front Head Electrical CB OS ...
Page 176: ...Chapter 9 Parts 9 26 Part No 750 184 Front Head Electrical CB OS ...
Page 179: ...Chapter 9 Parts Part No 750 184 9 29 Heavy Oil Piping 60 Steam CB LE ...
Page 180: ...Chapter 9 Parts 9 30 Part No 750 184 Heavy Oil Piping 60 Steam CB LE SEE TABLE NEXT PAGE ...
Page 181: ...Chapter 9 Parts Part No 750 184 9 31 Common Oil Parts Heavy Oil ...
Page 182: ...Chapter 9 Parts 9 32 Part No 750 184 Side Mounted Air Compressor Piping ...
Page 183: ...Chapter 9 Parts Part No 750 184 9 33 Air Compressor Piping CB OS ...
Page 185: ...Chapter 9 Parts Part No 750 184 9 35 Light Oil Piping ...
Page 186: ...Chapter 9 Parts 9 36 Part No 750 184 Light Oil Air Piping Front Head ...
Page 187: ...Chapter 9 Parts Part No 750 184 9 37 Light Oil Air Piping Front Head PAGE 9 31 ...
Page 191: ...Chapter 9 Parts Part No 750 184 9 41 Gas Train 125 150 HP ...
Page 193: ...Chapter 9 Parts Part No 750 184 9 43 Gas Train 200 HP ...
Page 195: ...Chapter 9 Parts Part No 750 184 9 45 Steam Pressure Controls ...
Page 196: ...Chapter 9 Parts 9 46 Part No 750 184 Hot Water Temperature Controls ...
Page 197: ...Chapter 9 Parts Part No 750 184 9 47 Water Column ...
Page 198: ...Chapter 9 Parts 9 48 Part No 750 184 Water Column ...
Page 199: ...Chapter 9 Parts Part No 750 184 9 49 Fireside Gaskets CB LE ...
Page 200: ...Chapter 9 Parts 9 50 Part No 750 184 Fireside Gaskets CB OS ...