Chapter 8 — Inspection and Maintenance
Part No. 750-184
8-7
F. FLAME SAFETY CONTROL
The microprocessor based control requires minimal maintenance because
the safety and logic timings are inaccessible. There also are not any
accessible contacts. Check to see that the retaining screw is securely holding
the chassis to the mounting base. Also check to see that the amplifier and
the program module are tightly inserted.
The relay's self-diagnostic ability includes advising when it or its plug-in
modules are at fault and require replacement.
Your spare control should be stored in a dry atmosphere and wrapped in
plastic. During an extended shutdown (e.g., seasonal), the active control
should be removed and stored. Moisture can cause problems with control
operation.
It is recommended that service be rotated between the active and a spare
control to assure a working replacement is available.
!
Warning
When replacing a control, be sure to lock out the main
power supply switch since the control is “hot” even though
the burner switch is off. Failure to follow these instructions
could result in serious personal injury or death.
Be sure the connecting contacts on the control and its base are not bent out
of position.
The flame detector lens should be cleaned as often as operating conditions
demand. Use a soft cloth moistened with detergent to clean the lens.
A safety check procedure should be established to test the complete
safeguard system at least once a month, or more often. Tests should verify
safety shutdown and a safety lockout upon failure to ignite the pilot, upon
failure to ignite the main flame, and upon loss of flame. Each of the
conditions should be checked on a scheduled basis.
The following tests should be used to test the complete safeguard system. If
the sequence of events is not as described, then a problem may exist.
Contact your local Cleaver-Brooks authorized representative for assistance.
Checking Pilot Flame Failure
Close the gas pilot shutoff cock. Also shut off the main fuel supply. Turn the
burner switch “on.”
The pilot ignition circuit will be energized at the end of the pre-purge period.
There should be an ignition spark, but no flame. Since there is no flame to
be detected, the program relay will signal the condition. The ignition circuit
will deenergize and the control will lock out on a safety shutdown. The flame
failure light (and optional alarm) will be activated. The blower motor will run
through the post-purge and stop.
Turn the burner switch off. Reset the safety switch. Reopen the gas pilot
shutoff cock and re-establish main fuel supply.
Checking Failure to Light Main Flame
Leave the gas pilot shutoff cock open. Shut off the main burner fuel supply.
Turn the burner switch on. The pilot will light upon completion of the pre-
Summary of Contents for CB Ohio Special 100 HP
Page 2: ...ii ...
Page 8: ...viii ...
Page 42: ...Chapter 2 Burner Operation and Control 2 22 Part No 750 184 ...
Page 116: ...Chapter 6 Adjustment Procedures 6 28 Part No 750 184 ...
Page 126: ...Chapter 8 Inspection and Maintenance 8 6 Part No 750 184 ...
Page 153: ...Chapter 9 Parts Part No 750 184 9 3 Insulated Front Head Model CB LE ...
Page 154: ...Chapter 9 Parts 9 4 Part No 750 184 Insulated Front Head Interior Model CB LE ...
Page 155: ...Chapter 9 Parts Part No 750 184 9 5 Insulated Inner Door Model CB OS ...
Page 156: ...Chapter 9 Parts 9 6 Part No 750 184 Insulated Rear Head CB LE ...
Page 157: ...Chapter 9 Parts Part No 750 184 9 7 Insulated Rear Head CB LE ...
Page 158: ...Chapter 9 Parts 9 8 Part No 750 184 Insulated Rear Head CB OS ...
Page 159: ...Chapter 9 Parts Part No 750 184 9 9 Dry Oven Model CB LE ...
Page 161: ...Chapter 9 Parts Part No 750 184 9 11 Motor Impeller Model CB LE ...
Page 162: ...Chapter 9 Parts 9 12 Part No 750 184 Front Head Linkage ...
Page 170: ...Chapter 9 Parts 9 20 Part No 750 184 Control Cabinet Hawk ICS ...
Page 171: ...Chapter 9 Parts Part No 750 184 9 21 Control Panel Standard ...
Page 172: ...Chapter 9 Parts 9 22 Part No 750 184 Entrance Box ...
Page 173: ...Chapter 9 Parts Part No 750 184 9 23 Front Head Electrical CB LE ...
Page 174: ...Chapter 9 Parts 9 24 Part No 750 184 Front Head Electrical CB LE ...
Page 175: ...Chapter 9 Parts Part No 750 184 9 25 Front Head Electrical CB OS ...
Page 176: ...Chapter 9 Parts 9 26 Part No 750 184 Front Head Electrical CB OS ...
Page 179: ...Chapter 9 Parts Part No 750 184 9 29 Heavy Oil Piping 60 Steam CB LE ...
Page 180: ...Chapter 9 Parts 9 30 Part No 750 184 Heavy Oil Piping 60 Steam CB LE SEE TABLE NEXT PAGE ...
Page 181: ...Chapter 9 Parts Part No 750 184 9 31 Common Oil Parts Heavy Oil ...
Page 182: ...Chapter 9 Parts 9 32 Part No 750 184 Side Mounted Air Compressor Piping ...
Page 183: ...Chapter 9 Parts Part No 750 184 9 33 Air Compressor Piping CB OS ...
Page 185: ...Chapter 9 Parts Part No 750 184 9 35 Light Oil Piping ...
Page 186: ...Chapter 9 Parts 9 36 Part No 750 184 Light Oil Air Piping Front Head ...
Page 187: ...Chapter 9 Parts Part No 750 184 9 37 Light Oil Air Piping Front Head PAGE 9 31 ...
Page 191: ...Chapter 9 Parts Part No 750 184 9 41 Gas Train 125 150 HP ...
Page 193: ...Chapter 9 Parts Part No 750 184 9 43 Gas Train 200 HP ...
Page 195: ...Chapter 9 Parts Part No 750 184 9 45 Steam Pressure Controls ...
Page 196: ...Chapter 9 Parts 9 46 Part No 750 184 Hot Water Temperature Controls ...
Page 197: ...Chapter 9 Parts Part No 750 184 9 47 Water Column ...
Page 198: ...Chapter 9 Parts 9 48 Part No 750 184 Water Column ...
Page 199: ...Chapter 9 Parts Part No 750 184 9 49 Fireside Gaskets CB LE ...
Page 200: ...Chapter 9 Parts 9 50 Part No 750 184 Fireside Gaskets CB OS ...