1-48
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
August 2005
Chapter 1 Install the Shelf and Common Control Cards
DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Step 1
For an ONS 15454 ETSI shelf, complete the following tasks as necessary:
•
Complete the
“DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)” task on page 1-48
you want to provision external alarms and/or controls with the AIC-I card.
•
Complete the
“DLP-G21 Install Timing Wires on the MIC-C/T/P (ETSI Only)” task on page 1-51
if you are provisioning external timing.
•
Complete the
“DLP-G22 Install LAN Wires on the MIC-C/T/P (ETSI Only)” task on page 1-52
create an external LAN connection. LAN wires or the LAN port on the TCC2/TCC2P card are
necessary to create an external LAN connection.
Step 2
For an ONS 15454 ANSI shelf, complete the following tasks as necessary:
•
Complete the
“DLP-G23 Install Alarm Wires on the Backplane (ANSI Only)” task on page 1-53
if
you are using an AIC or AIC-I card and are not using an AEP.
•
Complete the
“DLP-G24 Install Timing Wires on the Backplane (ANSI Only)” task on page 1-55
you are provisioning external timing.
•
Complete the
“DLP-G25 Install LAN Wires on the Backplane (ANSI Only)” task on page 1-56
to
create an external LAN connection. LAN wires or the LAN port on the TCC2/TCC2P card are
necessary to create an external LAN connection.
•
Complete the
“DLP-G26 Install the TL1 Craft Interface (ANSI Only)” task on page 1-57
to access
TL1 using the craft interface. Craft wires or the EIA/TIA-232 port on the TCC2/TCC2P card are
required to access TL1.
Stop. You have completed this procedure.
DLP-G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Step 1
Using 0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires, connect the alarm and control wires on the
appropriate pins of the DB-62 connector. The pin connectors, signal names, and functions are listed in
.
Purpose
This task installs alarm cables on the MIC-A/P on the ONS 15454 ETSI so
that you can provision external (environmental) alarms and controls with
the AIC-I card.
Tools/Equipment
DB-62 connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires
Prerequisite Procedures
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), page
1-28
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None