Technical Specifications
▀ Interface Specifications
▄ ASR 5000 Installation Guide
268
Figure 64.
SPIO CO Alarms Cable Assembly
Table 95.
CO Alarms Cable Pinout
CO Alarms IF Pin No.
Cable Wire Color
Cable Terminal Block Position No.
Signal
1
Black
1
Major Alarm - Normally closed
2
Orange
2
Major Alarm - Common
3
Red
3
Major Alarm - Normally open
4
Brown
4
Minor Alarm - Normally closed
5
Yellow
5
Minor Alarm - Common
6
Green
6
Minor Alarm - Normally open
7
Blue
7
Critical Alarm - Normally closed
8
Violet
8
Critical Alarm - Common
9
Gray
9
Critical Alarm - Normally open
10
Not wired
Not equipped
Not applicable
Electrical Characteristics
Each of the three dry-contact relay switches is rated to support a maximum switching current of 1A@30VDC. The relay
contacts should not directly connected to high current devices such as sirens and flashing lamps.
Summary of Contents for ASR 5000 Series
Page 9: ...Contents ASR 5000 Installation Guide ix Spare Component Recommendations 317 ...
Page 10: ......
Page 14: ......
Page 54: ......
Page 64: ......
Page 90: ......
Page 104: ......
Page 122: ......
Page 126: ......
Page 186: ......
Page 194: ......
Page 206: ......
Page 228: ......
Page 276: ......
Page 284: ......
Page 290: ......
Page 300: ...RoHS Compliance Statement Chassis ASR 5000 Installation Guide 300 Chassis ...
Page 301: ...RoHS Compliance Statement Fan Assembly ASR 5000 Installation Guide 301 Fan Assembly ...
Page 303: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 303 Full Product ...
Page 304: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 304 ...