Technical Specifications
Interface Specifications ▀
ASR 5000 Installation Guide ▄
267
Central Office Alarm Interface
The Central Office (CO) alarm interface is a 10-pin Molex connector supporting three dry-contact relay switches. The
three normally closed (NC) relays can support normally open (NO) or NC devices. The following two figures show the
pin-out details for this interface and the next figure shows an example CO alarm configuration.
Table 94.
SPIO CO Alarms Interface Pinout
Pin
Signal
1
Major Alarm - Normally closed
2
Major Alarm - Common
3
Major Alarm - Normally open
4
Minor Alarm - Normally closed
5
Minor Alarm - Common
6
Minor Alarm - Normally open
7
Critical Alarm - Normally closed
8
Critical Alarm - Common
9
Critical Alarm - Normally open
10
Not used
The 8-foot (2.4 meter) CO alarm cable shipped with the chassis supports redundant SPIO card installations. This “Y”
cable has two Molex connectors on one end that are keyed to fit into the CO Alarm interfaces in one direction only.
Each connector mates with one of the side-by-side SPIO cards. On the opposite end is a 9-pin terminal block that you
can mount to the telco cabinet or equipment rack frame.
The following figure and table display this cable assembly and its pinouts.
Summary of Contents for ASR 5000 Series
Page 9: ...Contents ASR 5000 Installation Guide ix Spare Component Recommendations 317 ...
Page 10: ......
Page 14: ......
Page 54: ......
Page 64: ......
Page 90: ......
Page 104: ......
Page 122: ......
Page 126: ......
Page 186: ......
Page 194: ......
Page 206: ......
Page 228: ......
Page 276: ......
Page 284: ......
Page 290: ......
Page 300: ...RoHS Compliance Statement Chassis ASR 5000 Installation Guide 300 Chassis ...
Page 301: ...RoHS Compliance Statement Fan Assembly ASR 5000 Installation Guide 301 Fan Assembly ...
Page 303: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 303 Full Product ...
Page 304: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 304 ...