Cabling the Switch Processor Input/Output Line Card
Connecting to the CO Alarm Interface ▀
ASR 5000 Installation Guide ▄
121
Electrical Characteristics
Each of the three dry-contact relay switches is rated to support a maximum switching current of 1A@30VDC. The relay
contacts should not directly connected to high current devices such as sirens and flashing lamps.
Important:
The CO alarm interface of the SPIO is suitable for connection to intra-building or unexposed wiring
or cabling only. This interface MUST NOT be metallically connected to interfaces that connect to the outside plant
(OSP) or its wiring. This interface is designed for use as an intra-building interface only (Type 2 or Type 4 ports as
described in GR-1089-CORE, Issue 5) and requires isolation from the exposed OSP cabling. The addition of Primary
Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
Central Office Alarm Wiring Example
The following figure depicts how the dry-contact relays can each control up to two external alarm indicators. In this
example, the CO alarm interface is connected to a CO Alarm Panel, where green LEDs are wired to indicate normal
operation, and red LEDs are wired to indicate an alarm condition.
Figure 40.
CO Alarm Interface Schematic
With all relays de-energized (normally closed), the green LED is illuminated. If an alarm relay is energized, the NO
(normally open) contact closes and the red LED is illuminated.
Summary of Contents for ASR 5000 Series
Page 9: ...Contents ASR 5000 Installation Guide ix Spare Component Recommendations 317 ...
Page 10: ......
Page 14: ......
Page 54: ......
Page 64: ......
Page 90: ......
Page 104: ......
Page 122: ......
Page 126: ......
Page 186: ......
Page 194: ......
Page 206: ......
Page 228: ......
Page 276: ......
Page 284: ......
Page 290: ......
Page 300: ...RoHS Compliance Statement Chassis ASR 5000 Installation Guide 300 Chassis ...
Page 301: ...RoHS Compliance Statement Fan Assembly ASR 5000 Installation Guide 301 Fan Assembly ...
Page 303: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 303 Full Product ...
Page 304: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 304 ...