Chassis Installation
Installing the Chassis ▀
ASR 5000 Installation Guide ▄
77
Figure 25.
Chassis Ground Terminals
Table 25.
Terminal and Cable specifications
Item
Description
1
Ground Terminal:
2-hole lug (0.186-inch posts, spaced 0.630-inch on center).
The method of connection is: chassis - lug - flat washer - nut (3/8-inch). The nut(s) must be torqued to 50 in-lb
(5.65 N-m).
2
Ground Cable:
Cable length: Not more than 70 feet (21.336 meters) one way.
Cable size: 6 AWG (minimum), stranded copper.