Cabling the Power Filter Units
Power Considerations ▀
ASR 5000 Installation Guide ▄
149
Table 48.
ASR 5000 PFU Wiring Diagram Descriptions
Item
Description
1
Two 2-hole lugs are required: one for return (RTN) and one for power (-VDC). The PFU 0.3125-inch posts spaced 0.88-
inch on center.
Method of connection: PFU - Flat Washer - Lug - Lock-Washer - Nut (9/16-inch). The nut(s) must be torqued to 50 in-lb.
(5.65 N-m).
The lug must be covered with heat shrink tubing. The heat shrink tubing should begin approximately 1 inch (25.4 mm)
before the lug and extend to within 0.5 inch (12.7 mm) of the lugs first hole. Slide the tubing over the cable end before
crimping the lug to the cable. Refer to the following figure.
Use the Panduit® lugs supplied with the chassis (LCD1-56C-E). Crimp them to the cable ends with a Panduit crimp tool
part number CT-920 (die color: green P37 (CD-920-1).
W
ARNING
:
The plastic terminal cover
must
be installed over power and return lugs at all times.
Die
angeschlossenen Kabelschuhe muessen mit der Plastikabdeckung gesichert sein.
2
Power Cables (PDP-to-Chassis):
Cable length: Not more than 9 feet (2.7 meters) one way
Voltage drop: 0.3v
Cable size: 1 AWG or greater
3
Power Cables (PDF-to-PDP):
Cable length: not more than 40 feet (12.2 meters) one way
Voltage drop: 0.3v
Cable size: 350,000 Circular Mils
Figure 50.
Power Lug
Summary of Contents for ASR 5000 Series
Page 9: ...Contents ASR 5000 Installation Guide ix Spare Component Recommendations 317 ...
Page 10: ......
Page 14: ......
Page 54: ......
Page 64: ......
Page 90: ......
Page 104: ......
Page 122: ......
Page 126: ......
Page 186: ......
Page 194: ......
Page 206: ......
Page 228: ......
Page 276: ......
Page 284: ......
Page 290: ......
Page 300: ...RoHS Compliance Statement Chassis ASR 5000 Installation Guide 300 Chassis ...
Page 301: ...RoHS Compliance Statement Fan Assembly ASR 5000 Installation Guide 301 Fan Assembly ...
Page 303: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 303 Full Product ...
Page 304: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 304 ...