EN
Alarm signals
In the event of a working defect, the system informs the user about the type of failure occurred.
The following table summarises the alarms, kind of problem and possible solution:
Regular checks should be carried out by the user, who should only contact the Authorized
Assistance Center if no solution is found.
Display
Kind of problem
Solution
ALAR 1
BLACK OUT
There is no power supply
As soon as the power supply is back, the Thermostove starts a
cooling cycle. After completing the cycle it starts working au-
tomatically
ALAR 2
PROBE
EXHAUST
The smokes sensor is broken or not con-
nected to the pcb
Contact an Authorized Assistance Center
ALAR 3
HOT
EXHAUST
Smokes temperature too high
Switch off the Thermostove, allow it to cool down and perform
ordinary cleaning. If the problem persists, contact an Authorized
Assistance Center for cleaning the Thermostove and the flue
ALAR 4
FAN
FAILURE
Smokes extractor blocked or broken
Contact an Authorized Assistance Center
ALAR 5
NO
LIGHTIN
The Thermostove cannot start up
This is the first light-up
Fill in the tank with pellets
Start up again
ALAR 6
NO
PELLET
The pellet thermostove switched off while
working
Fill in the tank with pellets
ALAR 7
SAFETY
THERMAL
The water temperature exceeds 90°C. The
circulating pump is blocked or there is no
water in the hydraulic system
Check the power supply on the pump.
Check limestone does not block the pump impeller
ALAR 8
FAILURE
DEPRESS
Obstructed flue
Clean the flue or check there are no obstructed grids near the
smokes exhaust
ALAR B
ERROR
TRIAC
COCLEA
The cochlea loads too much pellet
Contact an Authorized Assistance Center
ALAR C
PROBE
WATER
Water probe faulty
Contact an Authorized Assistance Center
ALAR D
HOT
WATER
Water temperature too high
Allow the thermostove to cool down. If the problem persists,
contact an Authorized Assistance Center and have the hydraulic
system checked
ALAR E
PRESS
WATER
Water pressure too high
Allow the thermostove to cool down. If the problem persists,
contact an Authorized Assistance Center and have the hydraulic
system checked
SERV
The Thermostove has worked for 1300
hours. Supplementary maintenance requi-
red
Contact an Authorized Assistance Center
Summary of Contents for IDRO 20
Page 56: ...56 IT NOTE Cod 001117...
Page 112: ...56 EN NOTES Cod 001117...
Page 168: ...56 FR NOTES Cod 001117...
Page 224: ...56 ES NOTAS Cod 001117...
Page 280: ...56 PT Cod 001117 NOTAS...
Page 336: ...56 DE Cod 001117 HINWEISE...
Page 392: ...56 DE NL 56 Cod 001117 OPMERKINGEN...
Page 393: ...GR GR1 CANADIAN IDRO 20 Cod 001117...
Page 395: ...GR 3 6 mm A1 UNI EN ISO 17225 2 3 42 kg...
Page 403: ...GR 11 UNI 10412 2 2009 C 60 C A1 3 4 M A2 3 4 M B1 1 2 B2 1 2 M A1 A2 B2 B1...
Page 404: ...GR 12 30 UNI CTI 8065 4...
Page 405: ...GR 13 1 bar 1 5 bar 1 14 1 bar 0 3 bar...
Page 406: ...GR 14 3 1 2 6 5 3 volt 4 3 3 4...
Page 407: ...GR 15 15 15 C 0 12 12 20 20 30 30 6 mm 30 mm 8 A1 UNI EN ISO 17225 2...
Page 429: ...GR 37 1 BLACK OUT 2 3 4 5 I 6 I 7 90 C 8 I TRIAC COC C D E 1300...
Page 430: ...GR 38 On Off On Off 1 BLACK OUT 1 10...
Page 431: ...GR 39 100 C ALAR DEP FAIL ALAR DEP FAIL 100 C ALAR SIC FAIL ALAR SIC FAIL 4A 2 5 bar 5 C 10...
Page 432: ...GR 40 2 3 15 30 60 90...
Page 433: ...GR 41 5 6 380 C 400 C 450 C 2 3 INOX 5...
Page 434: ...GR 42 60 90 20 24 28 32...
Page 435: ...GR 43 2 3 15 30 60 90 5 6...
Page 436: ...GR 44 2 3 INOX 5 380 400 450...
Page 437: ...GR 45 7 60 90 20 24 28 32...
Page 438: ...GR 46 2 3 3 15 AT T 16 16...
Page 439: ...GR 47 T...
Page 440: ...GR 48 OFF 1300 SERV SERV...
Page 441: ...GR 49 1 2 1 2 1 2 1 2 3 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 I 3 4 5 6...
Page 443: ...GR 51 1 2 1 2 1 2 3 1 2 3 1 1 1 1 1 2 3 1 2 3 1 2 1 65 C 40 C 80 C 50 55 C 50 55 C 2 1 2 1 2...
Page 444: ...GR 52 1 1 1 2 1 2 1 2 1 230 C 2 1 1 4 6 1 2 3 4 5 1 2 3 4 5...
Page 445: ...53 24 1 2 3 GR...
Page 446: ...GR 54 001117...