108/132 Operation
Bosch Rexroth AG
, SYEPS series 1X, RE 30201-B/07.2014
Fig. 81: Configuration example of an MTX control
9.4 HNC100 error messages - error handling
In the case of an error, the output “ready” (OUT 4) of the HNC100 changes to 0 V,
thus signaling to the higher-level control that an error has occurred. To be able to
analyze the error in more detail, an error code can be read out from the HNC100
over Profibus.
The error can be cleared by withdrawing the enable IN 1.
Table 31: Error codes
No.
Error description
Responsible
Cause of error
Measure
1-6
Bosch Rexroth
Internal HNC error
Inform Bosch Rexroth
8
Encoder cable break
Customer
Wiring defective or loose wire
connection
Inspect wiring to the position
transducer. Take electrical
measurements on connections. If
required, replace position transducer.
Connector X8M1 is not plugged in
Plug in and secure connector
9-11
Bosch Rexroth
Internal HNC error
Inform Bosch Rexroth
16
Impermissible operating mode
selected
Customer
PLC error - a value was
transmitted, which does not
correspond to a permitted
operating mode of the HNC100
Check the customer‘s PLC program.
Check Profibus transmission
for correct transmission of the
number format (high and low byte
interchanged).
25
Overflow of switching integrator Customer
Unfavorable traversing movements
and internal parameter settings
The switching integrator can be
switched off by means of R 460 =
0. This action also switches off the
automatic compensation for drift and
wear-related control errors.
26-41
Bosch Rexroth
Internal HNC error
Inform Bosch Rexroth