4–81
System Setup and Setpoints – 4
51V is a true three-phase function, in that the relay
incorporates separate integrating timers on each
phase.
The inverse time overcurrent function can be voltage
controlled (VC), voltage restrained (VR), or neither.
For voltage-controlled operation, the function is
not active unless the voltage is below the voltage
control setpoint. This philosophy is used to confirm
that the overcurrent is due to system fault. When
applied, most users will set voltage control limits in
the range of 0.7 to 0.9 per unit RMS voltage. When
voltage restraint is selected (See Figure 4-60, Voltage
Restraint (51VR) Characteristic), the pickup setting is
continuously modified in proportion to the collapsing
terminal voltage. The voltage restraint function is
well-suited to small generators with relatively short
time constants.
NOTE
:
The 51V function should be blocked by
fuse loss if in the voltage control mode
only. Fuse loss blocking is not desirable
for voltage restraint mode because the
pickup is automatically held at 100%
pickup during fuse loss conditions, and
operation will continue as normal.
The internally derived voltage used to realize the
voltage control or restraint feature depends on
the configured VT configuration and the Delta-Y
Transform setting (see Section 4.2 Setup System).
Table 4-7, Delta/Wye Transformer Voltage-Current
Pairs describes the calculation for the various
system VT configurations.
51V Inverse Time Phase Overcurrent with
Voltage Control/Restraint
Time-overcurrent relays, one per phase, are used
to trip circuits selectively and to time-coordinate with
other up- or downstream relays. For this function,
eight complete series of inverse time tripping
characteristics are included. The same descriptions
and nomenclature which are traditionally used with
electromechanical relays are used in the relay.
Thus, user may choose from four BECO curves
(BEDEF, BEINV, BEVINV, and BEEINV), four IEC
curves (IECI, IECVI, IECEI, and IECLT), and three
IEEE curves (MINV, VINV, EINV.) Within each
family, the operator selects time dial setting and
pickup (tap) setting, just as with electromechanical
relays. Ranges and increments are presented in
Figure 4-61.
The curves available for use are shown in Appendix
D,
Inverse Time Curves
. They cover a range from
1.5 to 20 times the pickup setting. An additional one
cycle time delay should be added to these curves
in order to obtain the relay operating time. Inverse
time curves saturate beyond 20 times pickup. For
currents in excess of 20 times pickup, operating
times are fixed at the 20 time pickup level. The
particular settings will be made by information from
short-circuit fault studies and knowledge of the
coordination requirements with other devices in the
system that respond to time overcurrent.
The pickup of the 51V is set in relay amps.
(Relay amps = primary amps ÷ CT ratio)
Selects one of the time curves as shown in Appendix D,
Inverse Time Curves
. The appropriate curve in the selected
family of curves is designated here.
Disable if neither voltage control nor voltage restraint is
desired. If voltage restraint is designated, the tap setting
is modified as shown in Figure 4-60. If voltage control is
designated, the 51V will only operate when the voltage is less
than the 51V voltage control setting specified below. When
applied, the voltage control is usually set in the range of 70%
to 90% of the nominal voltage.
51V PICKUP
Amps
51V CURVE
bedef beinv bevinv
51V TIME DIAL
51V VOLTAGE CONTROL
disable V_CNTL v_rstrnt
51V VOLTAGE CONTROL
Volts
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...