M‑3425A Instruction Book
6–58
81R Rate of Change of Frequency (#1, #2)
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
Hz/Sec
(0.10 to 20.00)
Time Delay
D
Cycles
(3 to 8160)
Negative Sequence
Voltage Inhibit
N
%
(0 to 99)
Programmed Outputs
Z
OUT
(1 to 8)
Expanded I/O
(9 to 23)
Test Setup:
1.
It is recommended that the 81 Function be used to establish a window of operation for the 81R
Function which is smaller than the actual sweep range of the frequency applied. This is accomplished
as follows:
NOTE
: The frequencies given are suggested for testing rates below 10 Hz/Sec. Higher rates will require
consideration of the capabilities of the test equipment involved.
a. Enable the
81#1
with a unique Output assigned, a Pickup Setting of 1 Hz greater than the
minimum frequency of the ramp and a time delay and seal-in time setting at minimum (This
will result in an operational window that is free of erroneous Hz/Sec measurements when the
voltage source begins or ends the sweep.).
b. Enable the
81#2
with a unique Output assigned, a Pickup Setting of 1 Hz less than the maximum
frequency of the ramp and a time delay and seal-in time setting at minimum (This will result in
an operational window that is free of erroneous Hz/Sec measurements when the voltage source
begins or ends the sweep.).
NOTE
: Using this setup, it is important to remember that the 81 elements being used will be operating
in the 81R blocking regions, and the 81R contact operation must be distinguished from the
81 contacts.
F81#1 Block
81R Active Region
F81#2 Block
56.5 Hz
57.5 Hz
60 Hz
62.5 Hz
63.5 Hz
c. Utilizing a jumper, connect the
81#1
and
81#2
assigned Outputs to a unique Input.
d. Set the 81R Function to block on this input.
2.
Determine the Function 81R Rate of Change of Frequency settings to be tested.
3.
Enter the Function 81R Rate of Change of Frequency settings to be tested utilizing either the HMI
or IPScom Communications Software.
4.
Disable all other functions prior to testing with the exception of Function 81. Refer to Section 4.4
System Setpoints, for details that describe disabling/enabling functions.
NOTE
: Testing of the 81R function requires a 3-phase voltage source capable of smoothly sweeping the
frequency of all voltages at a variable rate, continuously.
5.
Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.
6.
Set the three-phase voltages V
A
, V
B
, and V
C
to the
Nominal Voltage
(nominal frequency).
The
Nominal Voltage
value previously input to the relay is described in Section 4.2, Setup System
and should be recorded on Figure A-2, Setup System Record Form.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...