6–47
Testing – 6
64S 100% Stator Ground Protection by Low Frequency Injection
VOLTAGE INPUTS:
Adjustable 20 Hz Voltage Source (0 to 40 V)
CURRENT INPUTS:
Adjustable 20 Hz Current Source (0 to 100 mA)
TEST SETTINGS:
Total Current Pickup
P
mA
(2 to 75)
Real Component Pickup
P/2
mA
(2 to 75)
Time Delay
D
Cycles
(1 to 8160)
Voltage Restraint
(Enabled/Disabled)
Under Frequency Inhibit
(Enabled/Disabled)
Programmed Outputs
Z
OUT
(1 to 8)
Expanded I/O
(9 to 23)
Test Setup:
1.
Determine settings for F64S to be tested.
2.
Enter the settings for F64S into the relay to be tested using either the HMI or IPScom Communications
software.
3.
Disable all other functions prior to testing. Refer to Section 4.4 System Setpoints, for details that
describe disabling/enabling functions.
Pickup Test (Voltage Restraint Disabled and Under Frequency Inhibit Disabled)
:
1.
Enable the Total Current Pickup.
2.
Disable the Real Component of Current Pickup.
3.
Adjust the 20 Hz voltage generator to apply 25
s
0° volts across terminals 44 and 45.
4.
Press and hold the
TARGET RESET
pushbutton in, then slowly increase the 20 Hz current applied
to terminals 52 and 53 until the
27TN/59D/64S STATOR GND
LED illuminates, or the function status
indicator on the
Monitor Function Status
screen indicates that the function has picked up.
The 20 Hz current level should be equal to
P
mA
2 mA or
10%.
5
Release the
TARGET RESET
pushbutton.
6.
Disable the Total Current Pickup.
7.
Enable the Real Component of Current Pickup.
8.
Adjust the 20 Hz Voltage Generator to apply 25
s
0° Volts across terminals 44 and 45.
9.
Press and hold the
TARGET RESET
pushbutton in, then slowly increase the 20 Hz current at an
angle of 60 degrees leading the 20 Hz voltage applied to terminals 52 and 53 until the
27TN/59D/64S
STATOR GND
LED illuminates, or the function status indicator on the
Monitor Function Status
screen indicates that the function has picked up.
The 20 Hz current level should be equal to
P
mA
2 mA or
10%.
10.
Release the
TARGET RESET
pushbutton.
11.
Decrease the applied 20 Hz current to 0 mA and the applied 20 Hz voltage to 0 Volts.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...