4–53
System Setup and Setpoints – 4
25 Sync Check
NOTE
: The 25 function cannot be enabled under
any one of the following conditions:
•
67N (Residual Directional Overcurrent)
is enabled and the polarizing quantity
has been set to V
X
.
•
59D is enabled and the line side voltage
is set to V
X
.
•
59X is connected for turn-to-turn fault
protection or bus ground protection.
The Synchronism (Sync) Check function (25) is
used to ensure that the voltage magnitude, phase
angle and frequency of the generator (V1) and the
utility system (V
X
) are within acceptable limits before
the generator is synchronized with the system.
Generator voltage (V1) can be selected as A, B,
or C (line-to-ground and line-ground to line-line) or
AB, BC, or CA (line-to-line).
The sync check function includes phase angle, delta
frequency, and delta voltage checks.
Phase Angle Check
The phase angle is considered acceptable when
the selected sync phase voltage (V1) and system
voltage (V
X
) are within the Upper Volt Limit and
Lower Volt Limit window and the measured phase
angle is within the phase angle window.
Phase Angle Window is defined as twice the Phase
Angle Limit setting. For example, if the Phase Angle
Limit is set at 10 degrees, a phase angle window
of 20 degrees exists between –10 degrees and
+10 degrees. The logic diagram of the phase angle
check is shown in Figure 4-33.
Delta Voltage and Delta Frequency Check
Delta Voltage and Delta Frequency elements may
be individually enabled or disabled, as desired.
The Delta Voltage check will compare the absolute
difference between the selected sync phase voltage
(V1) and the measured system voltage (V
X
) with
the Delta Voltage Limit setting. Likewise, the Delta
Frequency measures the frequency difference
between V1 and V
X
voltage signals. The Phase
Angle Check, Delta Voltage and Delta Frequency
Check all combine through an appropriate timer with
the output directed to the programmed 25S output
contact. A logic diagram representing this logic is
presented in Figure 4-33.
Dead Line/Dead Bus Check
The Dead Volt Limit defines the Hot/Dead voltage
level used in Deadline/Dead Bus closing schemes.
When the measured V
X
voltage is equal to or below
the Dead Volt Limit, V
X
is considered dead. When
the measured V
X
is above the Dead Volt Limit, V
X
is considered hot. The opposite side of the breaker
uses the positive sequence voltage measurement
(V1) for 3-phase consideration in determining hot/
dead detection. Different combinations of hot line/
dead bus closings may be selected, depending on
how the buses are referenced. A logic diagram of
the Deadline/Dead Bus scheme is presented in
Figure 4-33.
The Dead V1, Dead V
X
, and Dead V1 & V
X
enable
are software switches used to enable the dead
line/dead bus logic. Further conditioning can be
performed on the dead detection logic by selecting
one or more input contacts (Dead Input Enable)
to control the enabled dead detection element.
For example, if INPUT2 (I2) is selected under the
Dead Input Enable screen, and both the Dead V1
and Dead V
X
elements are enabled, the dead check
timer will start when INPUT2 is activated, and either
V1 dead/V
X
hot or V1 hot/V
X
dead. This allows for
external control of the desired dead closing scheme.
Dead Input Enable selections are common to all
dead detection elements. If no inputs are selected
under the Dead Input Enable screen, and any dead
element is enabled, the dead check timer will start
immediately when the dead condition exists.
The 25S and 25D can be programmed to be sent
to two different contacts, if desired.
NOTE
: The 25 function does not produce a
target or LED and is accompanied by the
HMI message “F25 Function Operated”.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...