M‑3425A Instruction Book
6–8
21 Phase Distance (#1, #2 or #3)
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
Configuration C1
TEST SETTINGS:
Diameter
P
Ohms
(0.1 to 100)
1 Amp CT Rating
(0.5 to 500.0)
Offset
O
Ohms
(–100 to 100)
1 Amp CT Rating
(–500.0 to 500.0)
Impedance Angle
A
Degrees
(0 to 90)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
Output
(1 to 8)
Expanded I/O
(9 to 23)
VT Configuration
Line-Ground or Line-Line
NOTE:
It would be efficient to disable the element with the higher “reach” (Diameter plus Offset) setting
first (
lower current
), and test the lower reach setting operation, since the higher reach setting
operation can be tested without disabling the lower setting.
Test Setup:
1.
Determine the Function 21 Phase Distance settings to be tested.
2.
Enter the Function 21 Phase Distance settings to be tested utilizing either the HMI or IPScom
®
Communications Software.
3.
Disable all other functions prior to testing. Refer to Section 4.4 System Setpoints, for details that
describe disabling/enabling functions.
4.
Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.
5.
Connect test current inputs as shown in Figure 6-3, Current Inputs: Configuration C1.
6.
The level of current at which pickup operation is to be expected for an individual setting is determined
as follows:
a. Define “reach” as
R
ohms = (
P
ohms +
O
ohms) [
O
, usually set at zero ohms].
b. For Line-Ground configuration, define “current” as
I
= ((Selected Voltage)
I
R
ohms). The voltage
level may be selected based on the desired test current level. For Line-Line configuration, define
“current” as
I
= ((Selected Voltage/
S
3)
I
R
ohms).
Pickup Test
:
1.
Set the three-phase voltages to the Selected Voltage value from Step 6b above.
2.
Set the phase angle between the voltage and current inputs at (
A
) degrees from settings above (for
Line-Line configuration, set the phase angle at (
A
–30°).
3.
Press and hold the
TARGET RESET
pushbutton, then slowly increase the three-phase input currents
until the
21 PHASE DISTANCE
LED illuminates, or the pickup indicator illuminates on the IPScom
Function Status screen.
The level at which the
21 PHASE DISTANCE
actuates
should be equal to
I
calculated in Step 6 with
the resulting impedance
0.1 ohms or 5%.
4.
Release the
TARGET RESET
pushbutton, then decrease the three-phase input currents. The
assigned
OUTPUT
LEDs will extinguish.
5.
Press the
TARGET RESET
pushbutton to reset targets.
Time Test
:
1.
Connect a timer to output contacts
(Z)
so that the timer stops timing when the contacts
(Z)
close.
2.
Apply approximately 110% of the current (
I
) found in Step 6, and start timing. The contacts will close
after
D
cycles within
1 cycle or
1%.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...