–6–
M‑3425A Generator Protection Relay
PROTECTIVE FUNCTIONS (
cont
.)
Device
Setpoint
Number Function
Ranges
Increment
Accuracy
†
Negative Sequence Overcurrent
Definite Time
Pickup
3 to 100%
1%
0.5% of 5 A
(
0.5% of 1 A)
Time Delay
1 to 8160 Cycles
1
C
ycle
1 C
ycle or
1%
Inverse Time
Pickup
3 to 100%
1%
0.5 % of 5 A
(
0.5% of 1 A)
Time Dial Setting
1 to 95
1
3 Cycles or
3%
(K=
I
2
2
t)
Definite Maximum
Time to Trip
600 to 65,500 Cycles
1 Cycle
1 Cycle or
1%
Definite Minimum Time
12 Cycles
—
fixed
Reset Time (Linear)
1 to 600 Seconds
1 Second
1 Second or
1%
(from threshold of trip)
Pickup is based on the generator nominal current setting.
Stator Overload Protection
Time Constant #1, #2
1.0 to 999.9 minutes
0.1 minutes
Maximum Overload Current 1.00 to 10.00 A
0.01 A
0.1 A or
2%
(0.20 to 2.00 A)
Instantaneous Phase Overcurrent
Pickup #1, #2
0.1 to 240.0 A
0.1 A
0.1 A or
3%
(0.1 to 48.0 A)
(
0.02 A or
3%)
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
1 Cycle or
1%
When frequency f is < (f
nom
–5 ) Hz add an additional time of (1.5/f + 0.033) sec to the time delay accuracy.
Breaker Failure
Pickup
Phase Current
0.10 to 10.00 A
0.01 A
0.1 A or
2%
(0.02 to 2.00 A)
(
0.02 A or
2%)
Neutral Current
0.10 to 10.00 A
0.01 A
0.1 A or
2%
(0.02 to 2.00 A)
(
0.02 A or
2%)
Time Delay
1 to 8160 Cycles
1 Cycle
1 Cycle or
1%
50BF can be initiated from designated M‑3425A output contacts or programmable control/status inputs.
Definite Time Overcurrent
Pickup Phase A #1, #2
0.20 A to 240.00 A
0.01 A
0.1 A or
3%
(0.04 A to 48.00 A)
(
0.02 A or
3%)
Pickup Phase B #1, #2
(same as above)
Pickup Phase C #1, #2
(same as above)
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
1 Cycle or
1%
This function uses generator line‑side currents.
When 50DT function is used for split‑phase differential protection, 50BF, 87, and 87GD functions should not be
used, and the
I
A
,
I
B
and
I
C
inputs must be connected to the split phase differential currents.
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 A CT secondary rating.
50
DT
50
50
BF
50
BF‑Ph
50
BF‑N
46
49
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...