Installation – 5
5–31
6.
If IPScom returns an error message,
then determine the relay COM1
communication parameters as follows:
a.
From the relay Front Panel HMI
press
ENTER
. The relay will display:
VOLTAGE RELAY
VOLT curr freq v/hz
b.
Press the right arrow pushbutton
until the relay displays:
COMMUNICATION
W
stat COMM setup
V
c. Press
ENTER
. The relay will
display:
COM1 SETUP
COM1 com2 com3 com_adr
V
d. Press
ENTER
. The relay will
display:
COM1 BAUD RATE
W
baud_4800 baud_9600
Record the Baud Rate that is displayed
in all Caps: __________
e. Pres
EXIT
as necessary to exit
the HMI.
f.
Select the
Connect
menu item.
IPScom will display the
Serial Port
Dialog Screen
(Figure 3‑6).
g.
Verify the IPScom COM Port Baud
Rate is the same as relay COM1
Baud Rate.
h.
Verify that the
PC Comm Port
that is connected to the relay is
selected.
i. Select
Connect
. This action will
attempt to establish communication.
j.
If IPScom returns a “COM Opened
and Level #(1, 2 or 3) access
granted” then communications have
been established. Enter any valid
ISScom command(s) as desired.
To close the communication channel when
connected locally, select Communication/
Disconnect from the main screen menu
bar.
5.9
Initial Setup Procedure
The M‑3425A Generator Protection Relay is shipped
from the factory with all functions disabled (user will
only be able to enable purchased functions).
The Setup Procedure provided below is a suggested
setup procedure for initially entering settings into the
relay. While it is written for HMI‑equipped units, the
same procedure is applicable when setting the relay
through remote communication utilizing S‑3400
IPScom
®
Communications Software.
Following the Setup Procedure are several sections
which provide additional detail concerning the
settings required for proper commissioning.
Setup Procedure
NOTE
: Configuration Record forms are available in
Appendix A, Configuration Record Forms,
to record settings for future reference.
1.
Connect power to the relay’s rear power
terminals, as marked on the rear panel’s
power supply label and as shown in
Figures 5‑7 and 5‑8.
2. When power is initially applied, the
M‑3425A performs a number of self‑tests
to ensure its proper operation. During
the self‑tests, an “X” is displayed for
each test successfully executed. If all
tests are successful, the unit will briefly
display the word
PASS
. Then, a series
of status screens, including the model
number, software version number, serial
number, date and time as set in the
system clock, and the user logo screen
will be displayed. (Figure 2‑2 illustrates
this sequence of screens.)
3. If any test should fail, the DIAG LED will
flash the error code, or the error code will
be displayed on units equipped with the
HMI and the relay will not allow operation
to proceed. In such a case, the error
code should be noted and the factory
contacted. A list of error codes and their
descriptions are provided in Appendix
C,
Error Codes
. Assuming that various
voltage functions are enabled, and
there are no voltage inputs connected,
various voltage targets will be identified
as having operated
4. If remote communication is used, the baud
rate, address, and other parameters for the
communication ports must be set. Refer to
the instructions in Section 5.8, A
ctivating
Initial Local Communications
. Also
refer to
Chapter 3, IPScom
, on S‑3400
IPScom
®
Communications Software.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...