4–28
M‑3425A Instruction Book
When Input Activated Profiles is disabled, the Active Profile
can be selected using HMI or remote communication. When
enabled, the Active Profile is selected by the state of Input 5
and 6 (see Table 4-4).
This screen sets the active setpoint profile.
This screen initiates a copy of the Active Profile to any one
of the other profiles.
The secondary VT voltage when primary voltage is equal to
the rated
generator
voltage. V
nominal
=(
V
gen
rated I VT ratio)
for L-L VT connections. V
nominal
=(
V
gen rated I (
S
3 VT ratio))
for L-G VT connections.
The secondary CT current of the phase CT’s with rated
generator
current.
I
nom
= (VA I (Vgen rated(
S
3) )(CT ratio) )
Indicates VT connection. (See Figure 4-20, Three-Line
Connection Diagram.) When line-ground voltages are used,
functions 24, 27, and 59 may operate for line-ground faults.
If this is not desired, the line-gnd-to-line-line selection
should be used to prevent operation of these functions for
line-ground faults. When line-gnd-to-line-line is selected, the
relay internally calculates line-line voltages from line-ground
voltages for all voltage-sensitive functions. This line-gnd-to-
line-line selection should be used only for a VT line-to-ground
nominal secondary voltage of 69V (not for 120 V). For this
selection, the nominal voltage setting entered should be
line-line nominal voltage, which is
S
3 times line-ground
nominal voltage, and voltage function pickup setpoints
calculation should be made using line-to-line voltage.
INPUT ACTIVATED PROFILES
disable enable
ACTIVE SETPOINT PROFILE
COPY ACTIVE PROFILE
To_Profile_1
NOMINAL VOLTAGE
Volts
NOMINAL CURRENT
Amps
VT CONFIGURATION
line-line line-ground
line-gnd_to_line-line
4.2
Setup System
System setup data is required for proper operation
of the relay.
The Setup System consists of defining common
information like CT and VT ratios, nominal voltage
rating, nominal current rating and which profile is
the Active Profile, etc. Values are entered similar
to other setpoints. Configuration information is
common to all profiles, and should be entered
before setpoint and time settings.
NOTE:
Table 4-3 assumes ACTIVE INPUT STATE
set to default setting (close circuit = TRUE).
Input 5
Input 6
Selection
Open
Open
Profile 1
Closed
Open
Profile 2
Open
Closed
Profile 3
Closed
Closed
Profile 4
Table 4-3 Input Activated Profile Logic
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...