81 Frequency (#1, #2, #3, #4)
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
Hz
(50.00 to 67.00)
50 Hz Relay
(40.00 to 57.00)
Time Delay
D
Cycles
(3 to 65,500)
50 Hz Relay
Programmed Outputs
Z
OUT
(1 to 8)
Expanded I/O
(9 to 23)
NOTE
: It would be efficient to disable the elements with the settings nearest to nominal frequency first
(testing over or underfrequency functions).
Test Setup:
1.
Determine the Function 81 Frequency settings to be tested.
2.
Enter the Function 81 Frequency settings to be tested utilizing either the HMI or IPScom
®
Communications Software.
3.
Disable all other functions prior to testing. Refer to Section 4.4 System Setpoints, for details that
describe disabling/enabling functions.
4.
Connect test voltage inputs as shown in Figure 6-1, Voltage Inputs: Configuration V1.
5.
Set the three-phase voltages V
A
, V
B
, and V
C
to the
Nominal Voltage
(nominal frequency). The
Nominal
Voltage
value previously input to the relay is described in Section 4.2, Setup System and should be
recorded on Figure A-2, Setup System Record Form.
Pickup Test
:
1.
Press and hold the
TARGET RESET
pushbutton, then slowly increase/decrease the Input Voltage
(V
A
, V
B
, and V
C
) Frequency until the
FREQUENCY/ROCOF 81/81R
LED illuminates or the function
status indicator on the
Monitor Function Status
screen indicates that the function has picked up.
The frequency level will be equal to
P
Hz ±0.02 Hz only if
P
is within 3 Hz of F
nom
, otherwise,
0.1 Hz.
2.
Increase/decrease the Input Voltage (V
A
, V
B
, and V
C
) Frequency to nominal input frequency. The
OUTPUT
LED(s) will extinguish.
3. Press
TARGET RESET
pushbutton to reset targets.
Time Test
:
1.
Connect a timer to output contacts
(Z)
so that the timer stops timing when the contacts
(Z)
close.
2.
Apply (
P
+ or – 0.5) Hz and start timing. The contacts will close after
D
cycles within
2 cycles or
1%, whichever is greater.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...