4–96
M‑3425A Instruction Book
When 64B operates, indicating open brush
conditions, the 64F Function cannot detect a field
ground. For most generators, when the brushes of
the rotor shaft are lifted, the capacitance across the
field winding and the ground significantly reduces to
less than 0.15
m
F. The 64B Function analyzes this
capacitance-related signal, and initiates an output
contact when it detects an open brush condition.
Typically, this output is used to alert operating
personnel of an open brush condition. Ranges and
increments are presented in Figure 4-71. The typical
pickup setting is listed in Table 4-9, Typical Brush
Lift-Off Pickup Settings.
In order to assure correct setting, it is recommended
that the actual operating value be predetermined
during the final stage of the relay installation. By
introducing a brush-open condition, the actual
value can be easily obtained from the relay. The
following procedure can be used to obtain the actual
operating value of the 64B during an open brush
condition:
8
WARNING: Machine should be off-line
and field excitation should be off during the
capacitance measurement.
64B PICKUP
mV
64B DELAY
cycles
64B/F FREQUENCY
Hz
NOTE
: Field breaker should be closed for the
capacitance measurements.
1.
After installation has been completed,
determine the rotor capacitance, as
outlined for the 64F function.
2.
With the machine still off-line, apply
power to the relay and set the 64B/F
operating frequency in accordance with
the value listed in Table 4-8, Typical
Frequency Settings.
3.
Introduce a brush-open condition by
disconnecting the rotor brushes or lifting
the brushes from their ground. Observe
the 64B voltage value displayed by
IPScom or the relay. The displayed value
is the actual measured operating value
of the 64B function.
4.
To ensure correct operation and prevent
erroneous trips, the Pickup Setting for
the 64B Lift-off condition should be set
at 80–90% of the actual operating value.
The 64B/F Frequency is a shared setting common to both
the 64B and 64F Functions. If either function is enabled, this
setpoint is available, and should be set to compensate for the
amount of capacitance across the field winding and ground,
so that the measurement accuracy is improved.
To minimize measurement errors, the 64B/F frequency
should be set according to the amount of capacitance across
the field winding and the ground. Table 4-8 includes typical
settings of the frequency for capacitance, ranging from 1
m
F to 10
m
F.
Equivalent Brush Lift-Off
Capacitance
Typical Brush Lift-Off
Pickup Setting
0.05~0.25
m
F
2500 mV
Table 4-9 Typical Brush Lift-Off Pickup Setting
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...