4–93
System Setup and Setpoints – 4
64B/F Field Ground Protection
64F Field Ground Detection
Typical connections for Field Ground Protection
applications (including hydro turbine-generator
and brushless generators) is given in Figure
4-70. This function requires the connection of an
external coupler (M-3921). To improve accuracy
and minimize the effects of stray capacitance, the
M-3921 Field Ground Coupler should be mounted
close to the exciter. Connections from the coupler
to the relay should use low capacitance shielded
cable, and be as short as possible. Cable shield
should be terminated at the relay end to the
Relay Ground Stud (See Figure 5-9, External
Connections). If cabling between the coupler and
relay exceeds 100 feet, provisions should be made
for in circuit calibration to nullify the effects of cabling
capacitance. See Section 6.4, Auto Calibration, for
calibration procedure.
The Field Ground function provides detection of
insulation breakdown between the excitation field
winding and the ground. There are two pickup and
time delay settings, and one adjustable injection
frequency setting for the 64F function. The
adjustable frequency is provided to compensate for
the amount of capacitance across the field winding
and the ground so that the function accuracy is
improved. The minimum time delay should be
set greater than (2/IF + 1) seconds. Where IF =
Injection frequency. Ranges and increments are
presented in Figure 4-71.
Table 4-8 gives typical frequency settings based on
the rotor capacitance. The rotor capacitance can be
measured with a capacitance meter by connecting
the meter across the field winding to ground.
64F #1 PICKUP
kOhm
64F #1 DELAY
Cycles
64F #2 PICKUP
kOhm
64F #2 DELAY
Cycles
Factors Affecting 64F Performance
Some excitation systems include shaft voltage
suppressors which include capacitors that are
installed between the +/- field and ground. The
effect of these capacitors is given by the following
equation:
R
J
___1___
(2
π
IF C)
where:
R = Parallel winding-ground resistance
IF = Injection frequency setting
C = Capacitance value
To minimize this effect the following my be
implemented:
•
The injection frequency setting can be
reduced, however accuracy decreases
as a result.
•
With the concurrence of the exciter
manufacturer, surge capacitors rated at
a lower value may be installed.
This setting should not exceed 80% of the ungrounded
resistance value to prevent nuisance tripping. Typical setting
for the 64F #1 pickup element for alarming is 20 Kohms.
Typical delay setting for tripping is 800 cycles.
Typical setting for 64F #2 pickup element for tripping is 5
Kohms.
Typical delay setting for alarming is 180 cycles.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...