6–55
Testing – 6
Blocking on Stable Swing Test:
1.
While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of the Input
Currents to a point outside of the mho circle.
2.
While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of the Input
Currents to point
Z
0
in Figure 4-79.
3.
Press and hold the
TARGET RESET
pushbutton, then sweep past point
Z
1
.
When the impedance passes through point
Z
1
, verify that the
78 OUT OF STEP
LED illuminates,
or the function status indicator on the
Monitor Function Status
screen indicates that the function
has picked up.
4.
Pause testing until the delay timer has time to expire, then reverse the sweep direction and sweep
the current angle to point
Z
1
.
As point
Z
1
is crossed, verify output
Z
does not operate and the
78 OUT OF STEP
LED extinguishes
or the function status indicator on the
Monitor Function Status
screen indicates that the function
has reset.
6.
If testing is complete, then reduce voltages and currents to zero.
Pickup Test (Trip on mho Exit):
1.
Enable the
TRIP ON MHO EXIT
setting.
2.
While monitoring the Positive Sequence Impedance, set the magnitude and phase angle of the Input
Currents to point
Z
0
in Figure 4-79.
3.
Press and hold the
TARGET RESET
pushbutton, then sweep the current angle towards point
Z
1
.
When the impedance passes through point
Z
1
, verify that the
78 OUT OF STEP
LED illuminates or
the function status indicator on the
Monitor Function Status
screen indicates that the function has
picked up.
4.
Pause testing until the delay timer has time to expire, then continue to sweep the current angle to
beyond point
Z
2
. Verify that output
Z
does not operate as point
Z
2
is crossed.
5.
Sweep the impedance further towards point
Z
3
. Verify output
Z
operates as point
Z
3
is crossed, and
resets after the seal-in time delay has timed out.
6.
If testing is complete, then reduce voltages and currents to zero.
Summary of Contents for M-3425A
Page 1: ...Instruction Book M 3425A Generator Protection ...
Page 38: ...This Page Left Intentionally Blank ...
Page 43: ...This Page Left Intentionally Blank ...
Page 57: ...xiv M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 63: ...M 3425A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 95: ...M 3425A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 97: ...M 3425A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 123: ...M 3425A Instruction Book 3 28 Figure 3 30 View Sequence of Events Recorder Screen ...
Page 131: ...M 3425A Instruction Book 3 36 This Page Left Intentionally Blank ...
Page 162: ...4 31 System Setup and Setpoints 4 Figure 4 15 IPScom Relay Setup System Dialog Screen ...
Page 183: ...4 52 M 3425A Instruction Book Figure 4 32 Volts Per Hertz 24 Setpoint Ranges ...
Page 187: ...4 56 M 3425A Instruction Book Figure 4 34 Sync Check 25 Setpoint Ranges ...
Page 202: ...4 71 System Setup and Setpoints 4 Figure 4 50 49 Function Overload Curves ...
Page 203: ...4 72 M 3425A Instruction Book Figure 4 51 Stator Thermal Protection 49 Setpoint Ranges ...
Page 215: ...4 84 M 3425A Instruction Book Figure 4 62 Phase Overvoltage 59 Setpoint Ranges ...
Page 239: ...4 108 M 3425A Instruction Book Figure 4 80 Out of Step 78 Setpoint Ranges ...
Page 242: ...4 111 System Setup and Setpoints 4 Figure 4 82 Frequency 81 Setpoint Ranges ...
Page 261: ...M 3425A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 277: ...M 3425A Instruction Book 5 22 Figure 5 14 M 3425A Circuit Board ...
Page 278: ...Installation 5 5 23 Figure 5 15 M 3425A Circuit Board Expanded I O ...
Page 280: ...Installation 5 5 25 Figure 5 17 20 Hz Frequency Generator Housing Panel Surface Mount ...
Page 281: ...M 3425A Instruction Book 5 26 Figure 5 18 20 Hz Frequency Generator Housing Panel Flush Mount ...
Page 282: ...Installation 5 5 27 Figure 5 19 20 Hz Band Pass Filter Housing Panel Surface Mount ...
Page 283: ...M 3425A Instruction Book 5 28 Figure 5 20 20 Hz Band Pass Filter Housing Panel Flush Mount ...
Page 284: ...Installation 5 5 29 Figure 5 21 20 Hz Measuring Current Transformer 400 5 A CT ...
Page 421: ...D 2 M 3425A Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 422: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 423: ...D 4 M 3425A Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 424: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 427: ...D 8 M 3425A Instruction Book Figure D 5 BECO Definite Time Overcurrent Curve ...
Page 428: ...Inverse Time Curves Appendix D D 9 Figure D 6 BECO Inverse Time Overcurrent Curve ...
Page 429: ...D 10 M 3425A Instruction Book Figure D 7 BECO Very Inverse Time Overcurrent Curve ...
Page 430: ...Inverse Time Curves Appendix D D 11 Figure D 8 BECO Extremely Inverse Time Overcurrent Curve ...
Page 437: ...D 18 M 3425A Instruction Book Figure D 15 IEEE Extremely Inverse Time Overcurrent Curves ...
Page 469: ...F 30 M 3425A Instruction Book This Page Left Intentionally Blank ...
Page 479: ...H 2 M 3425A Instruction Book This Page Left Intentionally Blank ...