DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-38
D0–06DD2 I/O Wiring Diagram
The D0–06DD2 PLC has twenty sinking/sourcing DC inputs and sixteen sourcing DC outputs. The
following diagram shows a typical field wiring example. The AC external power connection uses four
terminals as shown.
Inputs are organized into four banks of four. Each bank has an isolated common terminal,
and may be wired as either sinking or sourcing inputs. The wiring example below shows all
commons connected together, but separate supplies and common circuits may be used.
All outputs share the same common. Note the requirement for external power.
9'&
6LQN
6RXUFH
DC Standard Inputs (X4-X23)
9'&
DC Pulse Outputs (Y0-Y1)
9'&
DC Standard Outputs (Y2-Y17)
Power input wiring
Input point wiring
Output point wiring
100-240
VAC
12-24
VDC
12-24 VDC
Sink
Source
0
4
12
16
Points
Ambient Temperature (
˚
C/
˚
F)
0
32
10
50
20
68
30
86
40
104
50
122
55˚C
131˚F
Y0 - Y7
1.0 A
Y10 - Y17
8
0.75A
Derating Chart for DC Outputs
9'&
6LQN
6RXUFH
High Speed Inputs (X0-X3)