Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-42
D0–06DD1–D I/O Wiring Diagram
These micro PLCs feature twenty DC inputs and sixteen sinking DC outputs. The following
diagram shows a typical field wiring example. The DC external power connection uses four
terminals at the left as shown.
Inputs are organized into
five banks of four. Each
bank has an isolated
common terminal, and
may be wired as either
sinking or sourcing
inputs. The wiring
example below shows
all commons connected
together, but separate
supplies and common
circuits may be used.
All outputs actually share
the same common. Note
the requirement for
external power.
0
4
12
16
Points
Ambient Temperature (
°
C/
°
F)
0
32
10
50
20
68
30
86
40
104
50
122
55°C
131°F
1.0 A
Y0-Y17
8
0.75A
Derating Chart for DC Outputs
Power
input wiring
Input point wiring
Output point wiring
D0-06DD1-D
+
-
12 - 24 VDC
+
-
N.C.
12-24V
12-24V
20W
6-27
VDC
20-28
VDC
12-24 VDC
Sink
Source
9'&
DC Pulse Outputs (Y0-Y1)
9'&
DC Standard Outputs (Y2-Y17)
9'&
6LQN
6RXUFH
Standard Input Circuit (X4-X23)
9'&
6LQN
6RXUFH
High Speed Inputs (X0-X3)