DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-326
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Network RX Read (NETRX) (IB-701)
Network RX Read performs the RX instruction with built-in interlocking with all other
Network RX (NETRX) and Network WX (NETWX) IBoxes in your program to simplify
communications networking. It will perform the RX on the specified Network #, which
corresponds to a specific unique Network Configuration (NETCFG) at the top of your
program.
For example, if you wish to read and write data continuously from 5 different slaves, you can
have all of these NETRX and NETWX instructions in ONE RUNG driven by SP1 (Always
On). They will execute round-robin style, automatically.
NETRX Parameters
• Network#: specifies the (CPU port’s, DCM’s, ECOM’s) Network # defined by the NETCFG
instruction
• Workspace: specifies a V-memory location that will be used by the instruction
• Slave ID: specifies the slave PLC that will be targeted by the NETRX instruction
• From Slave Element (Src): specifies the slave address of the data to be read
• Number of Bytes: specifies the number of bytes to read from the slave device
• To Master Element (Dest): specifies the location where the slave data will be placed in the master PLC
• Success: specifies a bit that will turn on once the request is completed successfully
• Error: specifies a bit that will turn on if the instruction is not successfully completed
DS
Used
HPP
N/A
Parameter
DL06 Range
Network#
K
K0-255
Workspace
V
See DL06 V-memory map - Data Words
Slave ID
K, V
K0-90: See DL06 V-memory map
From Slave Element (Src) X,Y,C,S,T,CT,GX,GY,V,P
See DL06 V-memory map
Number of Bytes
K
K1-128
To Master Element (Dest)
V
See DL06 V-memory map - Data Words
Success
X,Y,C,GX,GY,B
See DL06 V-memory map
Error
X,Y,C,GX,GY,B
See DL06 V-memory map
The Workspace parameter is an internal, private
register used by this IBox and MUST BE
UNIQUE in this one instruction and MUST
NOT be used anywhere else in your program.
Whenever this IBox has power, it will read
element data from the specified slave into the
given destination V-Memory buffer, giving other
Network RX and Network WX IBoxes on that
Network # a chance to execute.