ECOM100 Read Gateway Address (ECRDGWA) (IB-730)
ECOM100 Read Gateway Address will read the 4 parts of the Gateway IP address and store
them in 4 consecutive V-Memory locations in decimal format, on a leading edge transition to
the IBox.
ECRDGWA Parameters
• ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified
slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this
logical number
• Workspace: specifies a V-memory location that will be used by the instruction
• Success: specifies a bit that will turn on once the request is completed successfully
• Error: specifies a bit that will turn on if the instruction is not successfully completed
• Gateway IP Addr: specifies the starting address where the ECOM100’s Gateway Address will be
placed in 4 consecutive V-memory locations
DS
Used
HPP
N/A
Parameter
DL06 Range
ECOM100#
K
K0-255
Workspace
V
See DL06 V-memory map - Data Words
Success
X,Y,C,GX,GY,B
See DL06 V-memory map
Error
X,Y,C,GX,GY,B
See DL06 V-memory map
Gateway IP Address (4 Words)
V
See DL06 V-memory map - Data Words
The Workspace parameter is an internal,
private register used by this IBox and MUST
BE UNIQUE in this one instruction and
MUST NOT be used anywhere else in your
program.
Either the Success or Error bit parameter will
turn on once the command is complete.
In order for this ECOM100 IBox to function,
you must turn ON dip switch 7 on the
ECOM100 circuit board.