DL06 Micro PLC User Manual, 3rd Edition, Rev. E
3-29
Chapter 3: CPU Specifications and Operation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
DL06 System V-memory
System Parameters and Default Data Locations (V Data Type)
The DL06 PLCs reserve several V-memory locations for storing system parameters or certain
types of system data. These memory locations store things like the error codes, High-Speed I/O
data, and other types of system setup information.
System
V-memory
Description of Contents
Default Values / Ranges
Read
Only
R/W
V700-V707
Sets the V-memory location for option card in slot 1
N/A
R/W
V710-V717
Sets the V-memory location for option card in slot 2
N/A
R/W
V720-V727
Sets the V-memory location for option card in slot 3
N/A
R/W
V730-V737
Sets the V-memory location for option card in slot 4
N/A
R/W
V3630–V3707 The default location for multiple preset values for UP/DWN and UP Counter 1 or pulse catch function N/A
R/W
V3710-V3767 The default location for multiple preset values for UP/DWN and UP Counter 2
N/A
R/W
V7620
DV-1000 Sets the V-memory location that contains the value
V0 – V3760
R/W
V7621
DV-1000 Sets the V-memory location that contains the message
V0 – V3760
R/W
V7622
DV-1000 Sets the total number (1 – 32) of V-memory locations to be displayed
1 - 32
R/W
V7623
DV-1000 Sets the V-memory location containing the numbers to be displayed
V0 – V3760
R/W
V7624
DV-1000 Sets the V-memory location that contains the character code to be displayed
V0 – V3760
R/W
V7625
DV-1000 Contains the function number that can be assigned to each key
V-memory for X, Y, or C
R/W
V7626
DV-1000 Powerup operational mode
0,1, 2, 3, 12
R/W
V7627
Change preset value
0000 to 9999
R/W
V7630
Starting location for the multi–step presets for channel 1. The default value is 3630, which indicates
the first value should be obtained from V3630. Since there are 24 presets available, the default range
is V3630 – V3707. You can change the starting point if necessary.
Default: V3630
Range: V0- V3710
R/W
V7631
Starting location for the multi–step presets for channel 2. The default value is 3710, which indicates
the first value should be obtained from V3710. Since there are 24 presets available, the default range
is V3710 – V3767. You can change the starting point if necessary.
Default: V3710
Range: V0- V3710
R/W
V7632
Setup Register for Pulse Output
N/A
R/W
V7633
Sets the desired function code for the high speed counter, interrupt, pulse catch, pulse train, and
input filter.
This location can also be used to set the power-up in Run Mode option.
Default: 0060
Lower Byte Range: Range: 10
– Counter 20 – Quadrature 30 –
Pulse Out 40 – Interrupt 50 – Pulse
Catch 60 – Filtered discrete In.
Upper Byte Range: Bits 8–11, 14,
15: Unused, Bit 13: Power–up in
RUN, only if Mode Switch is in
TERM position. Bit 12 is used to
enable the low battery indications.
R/W
V7634
X0 Setup Register for High-Speed I/O functions for input X0
Default: 1006
R/W
V7635
X1 Setup Register for High-Speed I/O functions for input X1
Default: 1006
R/W
V7636
X2 Setup Register for High-Speed I/O functions for input X2
Default: 1006
R/W
V7637
X3 Setup Register for High-Speed I/O functions for input X3
Default: 1006
R/W
V7640
PID Loop table beginning address
V1200 - V7377
V10000-V17777
R/W
V7641
Number of PID loops enabled
1-8
R/W
V7642
Error Code - PID Loop Table
R
V7643-V7646 DirectSoft I-Box instructions work area
R
V7647
Timed Interrupt
R/W
V7653
Port 2: Terminate code setting Non-procedure
R/W
V7655
Port 2: Setup for the protocol, time-out, and the response delay time
R/W