DL06 Micro PLC User Manual, 3rd Edition, Rev. E
Chapter 2: Installation, Wiring, and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
2-44
D0–06DD2–D I/O Wiring Diagram
These micro PLCs feature twenty DC inputs and sixteen sourcing DC outputs. The following
diagram shows a typical field wiring example. The DC external power connection uses four
terminals at the left as shown.
Inputs are organized into five banks of four. Each bank has an isolated common terminal,
and may be wired as
either sinking or sourcing
inputs. The wiring example
below shows all commons
connected together, but
separate supplies and
common circuits may be
used.
All outputs actually share
the same common. Note
the requirement for
external power.
LOGIC
Koyo
06
C0
C4
C2
X1
X3
X4
X6
X11 X13 X14
X16
X21 X23 N.C.
C1
C3
X2
X5
X7
X10 X12
X15 X17 X20 X22
X0
N.C.
V1
V3
Y0
Y15
Y12
Y10
Y17
Y7
Y5
Y2
V0
V2
Y16
Y14
Y13
Y11
Y6
Y4
Y3
Y1
C0
+
-
LG
N.C.
N.C.
G
OUTPUT: Sourcing Output 12-24V
1.0A
INPUT: 12 - 24V
3 - 15mA
Y
X
PWR: 12-24V
20W
D0-06DD2-D
12 - 24
VDC
+
-
L L
L L
L L
L L
L L
L L
L L
L L
0
1
2
3
4
5
6
7
10 11 12 13 14 15 16
17 20 21 22
23
+
-
12 - 24 VDC
Power
input wiring
Input point wiring
Output point wiring
12-24 VDC
Sink
Source
9'&
6LQN
6RXUFH
Standard Input Circuit (X4-X23)
High Speed Inputs (X0-X3)
9'&
6LQN
6RXUFH
9'&
DC Pulse Outputs (Y0-Y1)
0
4
12
16
Points
Ambient Temperature (
˚
C/
˚
F)
0
32
10
50
20
68
30
86
40
104
50
122
55˚C
131˚F
Y0 - Y7
1.0 A
Y10 - Y17
8
0.75A
Derating Chart for DC Outputs
9'&
DC Standard Outputs (Y2-Y17)